Water system

Scioto Water Inc.-rose Hill

EPA ID OH7300303 · Scioto County · 8,861 people served

Purchased: Scioto Co. Regional Water Dist. #1 (Teays Valley Aquifer)
Groundwater

Scioto Water Inc.-rose Hill treats its own water from Purchased: Scioto Co. Regional Water Dist. #1 (Teays Valley Aquifer).

The system's record

Purchased: Scioto Co. Regional Water Dist. #1 (Teays Valley Aquifer)
Groundwater

Also purchases some water from Scioto Co. Regional Water District #1 (Teays Valley Aquifer (wells near SR 348)).

Wells: EPA lists 5 active wells. ODNR well logs locate 2 public-supply wells inside Scioto Water Inc.-rose Hill's wellhead protection zone, 64 to 66 ft deep, in sand & gravel. Zoom in to see them as dots.
Well-004Well-005Well-001Well-002Well-003
Active wells
5
Serves
8,861 people · Scioto County
EPA ID
OH7300303

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 4.6 ppb in 2025 (action level 15 ppb).

EPA record: no health-based violations since 2015.

2 violations of any kind logged since 2020: 2 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Present in 2 ZIP codes

Serves

Main water supplier in 1 ZIP code

Also present in 1 more ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Scioto Water Inc.-rose Hill does not buy water from another system on record; it treats its own source water.

1 system on record buys water from Scioto Water Inc.-rose Hill: Oak Hill, Village Of.

What the records show about Scioto Water Inc.-rose Hill

Who runs it

EPA's record says Scioto Water Inc.-rose Hill has 3,692 service connections and serves 8,861 people.

EPA classes it as a community water system, one that serves the same residents all year.

Its office telephone on EPA's record is 740-354-9140.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Scioto Water Inc.-rose Hill: aeration, chlorine disinfection, iron and manganese removal, fluoridation, ion-exchange softening, and sand or media filtration.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA's record shows no health-based violations for Scioto Water Inc.-rose Hill since 2015.

EPA logs 2 violations of any kind since 2020: 2 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Scioto Water Inc.-rose Hill was 4.6 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027.

EPA has 8 sampling periods on file for Scioto Water Inc.-rose Hill since 2016, the first ending in 2018; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Scioto Water Inc.-rose Hill sent EPA, 4,790 lines are counted.

Service lines in the inventory
MaterialLines
Lead0
Galvanized, needing replacement0
Unknown material3,513
Not lead1,277
All lines4,790

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

EPA's fifth national round of testing (UCMR 5) took 2 samples of the water entering the pipes of Scioto Water Inc.-rose Hill in 2023 and measured 29 PFAS. No PFAS was detected, PFOA and PFOS (federal limit 4 ng/L each) among them.

Ohio EPA's own statewide sampling tested 1 plant of Scioto Water Inc.-rose Hill (latest sample June 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Scioto Water Inc.-rose Hill's samples in 2019, the last year it was sampled, was 8 µg/L. The worst yearly average was 26.9 µg/L and the highest single sample was 30.2 µg/L, from 44 samples taken from 2012 to 2019.

For HAA5, the average in the last year sampled was 0 µg/L. The worst yearly average was 9.3 µg/L and the highest single sample was 12.2 µg/L, from 45 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L8 µg/L (2019)26.9 µg/L30.2 µg/L44
HAA560 µg/L0 µg/L9.3 µg/L12.2 µg/L45

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate: the highest of 8 samples was 1.97 mg/L (as nitrogen), in 2019, the last year sampled. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.

Arsenic was not detected in 3 samples (limit 10 µg/L).

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)81.97 mg/L10 mg/L0
Arsenic3not detected10 µg/L0
Combined radium11.7 pCi/L5 pCi/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 3 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L30 of 3not detected0
Carbon tetrachloride5 µg/L30 of 3not detected0
1,2-dichloroethane5 µg/L30 of 3not detected0
Trichloroethylene (TCE)5 µg/L30 of 3not detected0
Tetrachloroethylene (PCE)5 µg/L30 of 3not detected0
Vinyl chloride2 µg/L30 of 3not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 3 of 3 samples, highest 29 µg/L (limit 2,000). Not detected: atrazine, alachlor, chromium, cadmium, mercury, selenium, and thallium, in 3 samples each.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L30 of 3not detected0
AlachlorFarm chemical2 µg/L30 of 3not detected0
ChromiumMetal100 µg/L30 of 3not detected0
CadmiumMetal5 µg/L30 of 3not detected0
BariumMetal2,000 µg/L33 of 329 µg/L0
MercuryMetal2 µg/L30 of 3not detected0
SeleniumMetal50 µg/L30 of 3not detected0
ThalliumMetal2 µg/L30 of 3not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 0 of 963 routine total coliform samples taken in the distribution system at Scioto Water Inc.-rose Hill tested positive (0%); in 2019, the last year on file, 0 of 120 did.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Scioto Water Inc.-rose Hill adjusts the fluoride level to the recommended level for preventing tooth decay.

EPA's treatment table lists fluoridation among the steps at Scioto Water Inc.-rose Hill.

Measured fluoride: 0.92 mg/L on average at the plant's entry points in 2019 (in the range dentists aim for); samples ran from 0.92 to 1.07 mg/L across 3 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

Lithium

Lithium was not detected in 2 UCMR 5 samples at Scioto Water Inc.-rose Hill, last sampled in 2023 (the method reports from 9 µg/L).

Lithium is not regulated. EPA's draft health reference level is 10 µg/L, and it occurs naturally in deep groundwater, so well systems in the northwest run highest.

Source: EPA UCMR 5 occurrence data (final release, August 2026), samples from 2023 to 2025.

How well the service area is mapped

EPA estimated the service area of Scioto Water Inc.-rose Hill with a computer model rather than drawing it from the utility's map, so its edges are approximate.

Counting the people who live in the ZIP codes it overlaps, this atlas estimates 1,281 residents are inside the boundary, 14% of the 8,861 people Scioto Water Inc.-rose Hill reports serving. With so much of its territory outside the polygon, part of the system shows on the map as private wells.

The resident count is an estimate from 2020 Census ZIP-code populations, not a count of customers.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

On the map

Show this system's territory on the map — 2 ZIP codes in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH7300303 (EPA ECHO).

Scioto Water Inc.-rose Hill's own pages: water1.org

Quick answers

Where does Scioto Water Inc.-rose Hill get its water?

Scioto Water Inc.-rose Hill treats its own water from Purchased: Scioto Co. Regional Water Dist. #1 (Teays Valley Aquifer).

How many people does Scioto Water Inc.-rose Hill serve?

Scioto Water Inc.-rose Hill serves about 8,861 people, and is the main water system for 1 ZIP code.

Cite this page

Cite this page as:

Cracked Buckeye, "Scioto Water Inc.-rose Hill · OH7300303", https://crackedbuckeye.com/water/OH7300303/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31