Water system

Troy City

EPA ID OH5501612 · Miami County · 26,305 people served · owned by a local government

Great Miami Buried Valley Aquifer (wells)
Groundwater

Troy City treats its own water from Great Miami Buried Valley Aquifer (wells).

The system's record

Great Miami Buried Valley Aquifer (wells)
Groundwater
Wells: EPA lists 10 active wells. ODNR well logs locate 8 public-supply wells inside Troy City's wellhead protection zone, 68 to 125 ft deep, in sand & gravel and gravel/sand/clay. Zoom in to see them as dots.
Well EWell EWell EWell EWell EWell WWell WWell WWell 16Well 19
Aquifer
Great Miami Buried Valley Aquifer
Active wells
10
Serves
26,305 people · Miami County
EPA ID
OH5501612

About this area's water

Adams Street Bridge over the Great Miami River in Troy, Ohio
Adams Street Bridge over the Great Miami River in Troy, OhioPhoto: Antony-22, CC BY-SA 4.0 · Wikimedia Commons
Did you know
  • Troy's ten production wells sit under a public golf course (Miami Shores) and a city park, tapping the glacial-outwash sand and gravel buried along the ancient course of the Great Miami River.
  • Troy does not fluoridate its water - twice, by referendum, residents voted against it. The 0.38 ppm of fluoride in the tap is what nature put in the aquifer and treatment left behind.
  • Water rates in Troy have not changed since January 1, 2017, even as the city raised sewer rates for 2026.
  • The plant has treatment capacity for 16 million gallons a day but averaged 3.66 million in 2025 and peaked at 5.62 million - roughly a third of what it could produce.
  • Troy's own utility fee schedule contains an order-of-magnitude typo, describing 1,000 cubic feet of sewage as 'approximately 75,000 gallons.' It is about 7,480.

Source: troyohio.govtroyohio.govtroyohio.gov

History6
  • 1999Plant treatment expansion projects completed, raising future treatment capacity to 16 million gallons per day; emergency power added to the plant and both well fields.
  • 2017A new 0.75 million gallon elevated tower on W. Stanfield Road is completed to improve fire flows and reliability in the Extra High Service pressure zone. Water rates set on 1/1/2017 are still the…
  • 2022November: construction begins on a $11.8 million expansion of the city's wastewater treatment plant, after two years of planning.
  • 2023Troy participates in the fifth round of the federal Unregulated Contaminant Monitoring Rule (UCMR 5), which includes PFAS sampling; results are available from the water department on request and are…
  • 2024October: Phase 1 of the wastewater plant expansion goes online, raising capacity from 7 to 9 MGD, adding a third aeration tank and nutrient-removal technology, and moving the plant from Class III to…
  • 2025Troy holds an unconditioned license to operate; sampling for 34 contaminants finds most non-detect. Sewer rates rise effective 1/1/2026 while water rates stay at their 2017 level.

Source: troyohio.govtroyohio.govtroyohio.gov

Treatment & pressure

How it is treated

Ten production wells at Miami Shores Golf Course and Troy Community Park draw from the buried valley sand-and-gravel aquifer associated with the Great Miami River. Raw well water is pumped to the Troy Water Treatment Plant at 300 E. Staunton Road, where it is softened, clarified, disinfected and…

Source: troyohio.govtroyohio.govtroyohio.gov

Water pressure

No psi figures published. The city says only that after treatment water is 'maintained at a sufficient pressure for residential, commercial, industrial, and firefighting…

Source: troyohio.gov

What it costs

$6.14 per 1,000 gallons

Typical household bill about $23 a month for water.

CAUTION - Troy bills water by the cubic foot, not the gallon. Water rates, effective 1/1/2017 (Codified Ordinances 913.01) and unchanged since: inside city, 0-200 cf is covered by…

Source: troyohio.govtroyohio.gov

Water quality & impurities10
ContaminantLevelLimitYear
Total trihalomethanes (TTHM)
Range 18.7-20.9 ppb. No violation.
20.9 ppb802025
Haloacetic acids (HAA5)
Range <2.8-3.0 ppb.
3.0 ppb602025
Total chlorine
Range 0.84-1.00 ppm.
0.96 ppm4 (MRDL)2025
Tetrachloroethylene (PCE)
Range <0.07-0.2 ppb. Typical source: discharge from industrial chemical factories.
0.2 ppb52025
Trichloroethylene (TCE)
Range <0.08-0.1 ppb.
0.1 ppb52025
cis-1,2-Dichloroethylene
Range <0.04-0.4 ppb.
0.4 ppb702025
Fluoride
Naturally occurring - Troy does not add fluoride. The city says naturally occurring fluoride persists through treatment…
0.38 ppm42025
Barium
Erosion of natural deposits.
0.0469 ppm22025
Nitrate
Well below the MCL.
0.244 ppm102025
Lead (90th percentile)
0 of 30 samples over the action level. Copper 90th percentile 0.0346 ppm, 0 of 30 over the 1.3 ppm action level. A…
0.5 ppb15 (action…2025

Source: troyohio.govtroyohio.gov

EPA compliance record

Lead at the tap: 90th-percentile result 0.5 ppb in 2025 (action level 15 ppb).

EPA record: no health-based violations since 2015.

Projects & plans6

Recent and current work

  • Water treatment plant expansion to 16 MGD capacity · 1999 · completed
    Treatment expansion projects completed in 1999 allowing future capacity up to 16 MGD; emergency power added to the plant and both well fields. No cost…
  • 0.75 MG elevated tower, W. Stanfield Road · 2017 · completed
    Built to improve fire flows and system reliability in the Extra High Service pressure zone. No cost published.
  • Wastewater treatment plant expansion, Phase 1 · $12 million · 2024 · completed
    Construction began November 2022, online October 2024. Raised capacity from 7 to 9 MGD, replaced components up to 50 years old, added a third aeration tank and…
  • Sewer rate increase effective 1/1/2026 · 2026 · completed
    City sewer volume charge raised to $50.41 per 1,000 cubic feet with an $11.00 minimum on a 5/8-inch meter (Codified Ordinances 915.10); rural rates to $63.01.…

Source: troyohio.govtroyohio.govtroyohio.gov

Planned or needed

  • Wastewater treatment plant expansion, Phase 2 · 2025 · planned
    Announced in October 2024 as scheduled for completion in 2025; replaces outdated sludge-handling equipment. No separate cost published and no completion notice…
  • Capital Improvements Plan · planned
    The city publishes a Capital Improvements Plan as an ArcGIS dashboard map rather than a document; individual water and sewer projects, costs and years could…

Source: troyohio.govtroyohio.gov

Supply stress

Troy's own water quality report states that the wellfield sits above a buried valley aquifer providing 'limited natural protection from contaminations infiltrating into the aquifer,' and that the aquifer supplying Troy is therefore 'considered to be highly susceptible to contamination.' The city runs a comprehensive wellhead protection…

Source: troyohio.govtroyohio.gov

Sewers

Sanitary

The City of Troy Wastewater Treatment Plant at 1400 Dye Mill Road is a conventional activated sludge plant run in a plug-flow valve configuration, discharging treated effluent to the Great Miami River under an NPDES permit. The city's page still lists a design capacity of 7 MGD with about 5.5 MGD average flow; the Phase 1 expansion that…

Storm

Not documented. No storm water utility, storm sewer rate or separate storm system description appears in Troy's master fee schedule or on the wastewater and utility pages reviewed.

Source: troyohio.govtroyohio.govtroyohio.gov

Sourcesverified

Compiled from the utility's own reports and public records, then independently re-checked against primary sources.

Main supplier in 1 ZIP code

Serves

Main water supplier in 1 ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Troy City does not buy water from another system on record; it treats its own source water.

3 systems on record buy water from Troy City: Miami Co-camp Troy, Miami Co-n25a Extension, West Milton Village.

What the records show about Troy City

Who runs it

EPA's record describes Troy City as owned by a local government. It has 11,457 service connections and serves 26,305 people.

EPA classes it as a community water system, one that serves the same residents all year.

EPA's record says it has substantially implemented source water protection under Ohio's program, dating the program from 2022. Its office telephone on EPA's record is 937-339-4826.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Troy City: corrosion control, coagulation and settling, chlorine disinfection, lime softening, and sand or media filtration.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA's record shows no health-based violations for Troy City since 2015.

EPA logs no violations of any kind for Troy City since 2020.

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Troy City was 0.5 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027.

The highest result on file is 5.1 ppb, in the period ending December 2016.

EPA has 4 sampling periods on file for Troy City since 2016, the first ending in 2016; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Troy City sent EPA, 12,157 lines are counted.

Service lines in the inventory
MaterialLines
Lead3
Galvanized, needing replacement117
Unknown material2,811
Not lead9,226
All lines12,157

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

EPA's fifth national round of testing (UCMR 5) took 3 samples of the water entering the pipes of Troy City in 2023 and measured 29 PFAS. No PFAS was detected, PFOA and PFOS (federal limit 4 ng/L each) among them.

Ohio EPA's own statewide sampling tested 1 plant of Troy City (latest sample July 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

Ohio EPA's current sampling status map lists 1 plant of Troy City as sampled, most recently May 2026.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Troy City's samples in 2019, the last year it was sampled, was 19.5 µg/L. The worst yearly average was 29.9 µg/L and the highest single sample was 35 µg/L, from 43 samples taken from 2012 to 2019.

For HAA5, the average in the last year sampled was 4.8 µg/L. The worst yearly average was 6.2 µg/L and the highest single sample was 6.2 µg/L, from 43 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L19.5 µg/L (2019)29.9 µg/L35 µg/L43
HAA560 µg/L4.8 µg/L6.2 µg/L6.2 µg/L43

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate: the highest of 10 samples was 0.46 mg/L (as nitrogen) in 2012; in 2019, the last year sampled, nitrate was not detected. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.

Arsenic was not detected in 4 samples (limit 10 µg/L).

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)100.46 mg/L10 mg/L0
Arsenic4not detected10 µg/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. tetrachloroethylene (PCE) was detected in 1 of 41 samples, highest 0.87 µg/L (limit 5). Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, and vinyl chloride were not detected in 41 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L410 of 41not detected0
Carbon tetrachloride5 µg/L410 of 41not detected0
1,2-dichloroethane5 µg/L410 of 41not detected0
Trichloroethylene (TCE)5 µg/L410 of 41not detected0
Tetrachloroethylene (PCE)5 µg/L411 of 410.87 µg/L0
Vinyl chloride2 µg/L410 of 41not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 2 of 4 samples, highest 24 µg/L (limit 2,000). Not detected: atrazine in 3 samples, alachlor in 3 samples, chromium in 5 samples, cadmium in 5 samples, mercury in 4 samples, selenium in 4 samples, thallium in 4 samples.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L30 of 3not detected0
AlachlorFarm chemical2 µg/L30 of 3not detected0
ChromiumMetal100 µg/L50 of 5not detected0
CadmiumMetal5 µg/L50 of 5not detected0
BariumMetal2,000 µg/L42 of 424 µg/L0
MercuryMetal2 µg/L40 of 4not detected0
SeleniumMetal50 µg/L40 of 4not detected0
ThalliumMetal2 µg/L40 of 4not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 1 of 2,824 routine total coliform samples taken in the distribution system at Troy City tested positive (0.04%); in 2019, the last year on file, 0 of 360 did. E. coli was never found in the 1 sample tested for it.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Troy City has fluoride from natural sources, but at a level below what is recommended for preventing tooth decay, and does not adjust it. The level it reports is 0.43 mg/L.

EPA's treatment table lists no fluoridation step at Troy City.

Measured fluoride: 0.25 mg/L on average at the plant's entry points in 2018 (too little to protect teeth); samples ran from 0.25 to 0.46 mg/L across 6 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

Lithium

Lithium was not detected in 2 UCMR 5 samples at Troy City, last sampled in 2023 (the method reports from 9 µg/L).

Lithium is not regulated. EPA's draft health reference level is 10 µg/L, and it occurs naturally in deep groundwater, so well systems in the northwest run highest.

Source: EPA UCMR 5 occurrence data (final release, August 2026), samples from 2023 to 2025.

Water and sewer bills

Ohio EPA's 2023 rate survey puts the water bill at Troy City for a household using 5,000 gallons a month at $402 a year, about $34 a month.

The sewer bill in the same survey is $359 a year at 5,000 gallons a month.

Annual bills, 2023
UseWater, per yearSewer, per year
2,500 gallons a month$183$184
5,000 gallons a month$402$359
8,000 gallons a month$663$568

The survey lists it as “Troy”. These are inside-city rates and annual bills at the use shown.

Source: Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State University, May 2025).

How well the service area is mapped

The service area drawn on the map for Troy City comes from the utility's own map.

Counting the people who live in the ZIP codes it overlaps, this atlas estimates 23,857 residents are inside the boundary, 91% of the 26,305 people Troy City reports serving.

The resident count is an estimate from 2020 Census ZIP-code populations, not a count of customers.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

Photograph

Adams Street Bridge over the Great Miami River in Troy, Ohio
Adams Street Bridge over the Great Miami River in Troy, OhioPhoto: Antony-22 · CC BY-SA 4.0 · Wikimedia Commons

On the map

Show this system's territory on the map — 1 ZIP code in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH5501612 (EPA ECHO).

Troy City's own pages: troyohio.gov, daytonohio.gov

Notable facts: troyohio.gov, troyohio.gov, troyohio.gov, troyohio.gov

History: troyohio.gov, troyohio.gov, troyohio.gov, troyohio.gov

Water quality: troyohio.gov, troyohio.gov

Planned work: troyohio.gov, troyohio.gov

Water pressure: troyohio.gov

Capital projects: troyohio.gov, troyohio.gov, troyohio.gov

Rates: troyohio.gov, troyohio.gov

Sewers: troyohio.gov, troyohio.gov, troyohio.gov

Treatment: troyohio.gov, troyohio.gov, troyohio.gov, troyohio.gov

Supply stress: troyohio.gov, troyohio.gov

Quick answers

Where does Troy City get its water?

Troy City treats its own water from Great Miami Buried Valley Aquifer (wells).

How many people does Troy City serve?

Troy City serves about 26,305 people, and is the main water system for 1 ZIP code.

Who owns Troy City?

Troy City is owned by a local government.

Is there lead in Troy City water?

In 2025 testing, Troy City's 90th-percentile lead level in tap samples was 0.5 ppb (the federal action level is 15 ppb). 0 of 30 samples over the action level. Copper 90th percentile 0.0346 ppm, 0 of 30 over the 1.3 ppm action level. A….

How much fluoride is in Troy City water?

Troy City reported fluoride at 0.38 ppm in 2025. Naturally occurring - Troy does not add fluoride. The city says naturally occurring fluoride persists through treatment….

Cite this page

Cite this page as:

Cracked Buckeye, "Troy City · OH5501612", https://crackedbuckeye.com/water/OH5501612/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31