Water system

Hamler Village

EPA ID OH3500312 · Henry County · 580 people served · owned by a local government

Groundwater wells (2 wells)
Groundwater

Hamler Village treats its own water from Groundwater wells (2 wells).

The system's record

Groundwater wells (2 wells)
Groundwater
Wells: EPA lists 2 active wells.
Well 4Well 7
Active wells
2
Serves
580 people · Henry County
EPA ID
OH3500312

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 0 ppb in 2025 (action level 15 ppb).

EPA health-based violations since 2015:

  • 2026Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.099 MG/L (limit 0.08 MG/L) · known
  • 2025Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.096 MG/L (limit 0.08 MG/L) · known
  • 2025Lead and Copper Rule · water quality limits for corrosion control not met · known
  • 2024Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.104 MG/L (limit 0.08 MG/L) · known
  • 2023Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.122 MG/L (limit 0.08 MG/L) · known
  • 2023Lead and Copper Rule · water quality limits for corrosion control not met · returned to compliance
  • 2022Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.126 MG/L (limit 0.08 MG/L) · known
  • 2022Lead and Copper Rule · water quality limits for corrosion control not met · returned to compliance

3 more problems in this period not listed. EPA's count of 24 includes 13 repeat quarterly violations of the problems listed.

52 violations of any kind logged since 2020: 26 for required testing that was missed or reported late; 5 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 21 health-based.

Present in 1 ZIP code

Serves

Main water supplier in 1 ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Hamler Village does not buy water from another system on record; it treats its own source water.

No other system is on record buying water from Hamler Village.

What the records show about Hamler Village

Who runs it

EPA's record describes Hamler Village as owned by a local government. It has 280 service connections and serves 580 people.

EPA classes it as a community water system, one that serves the same residents all year.

EPA's record says it has substantially implemented source water protection under Ohio's program, dating the program from 2025. Its office telephone on EPA's record is 419-274-7651.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Hamler Village: aeration, corrosion control, chlorine disinfection, ion-exchange softening, and sand or media filtration.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA counts 24 health-based violations for Hamler Village since 2015. Health-based means a contaminant above its legal limit or a required treatment step not carried out. They fall into 11 separate problems (one contaminant or rule in one year); the table lists the 8 most recent.

EPA logs a violation for each compliance period a problem lasts, so the count of 24 includes 13 repeat entries of the problems listed.

EPA logs 52 violations of any kind since 2020: 26 for required testing that was missed or reported late; 5 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 21 health-based.

Health-based violations since 2015, most recent first
YearContaminant or ruleKindMeasuredLimitStatus in EPA's record
2026Total trihalomethanes (TTHM)above the legal limit on average0.099 mg/L0.08 mg/Lknown
2025Total trihalomethanes (TTHM)above the legal limit on average0.096 mg/L0.08 mg/Lknown
2025Lead and Copper Rulewater quality limits for corrosion control not metnot on filenot on fileknown
2024Total trihalomethanes (TTHM)above the legal limit on average0.104 mg/L0.08 mg/Lknown
2023Total trihalomethanes (TTHM)above the legal limit on average0.122 mg/L0.08 mg/Lknown
2023Lead and Copper Rulewater quality limits for corrosion control not metnot on filenot on filereturned to compliance
2022Total trihalomethanes (TTHM)above the legal limit on average0.126 mg/L0.08 mg/Lknown
2022Lead and Copper Rulewater quality limits for corrosion control not metnot on filenot on filereturned to compliance

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Hamler Village was 0 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027. A result of 0 means at least nine in ten of the homes sampled had no lead detected.

The highest result on file is 2 ppb, in the period ending December 2019.

EPA has 13 sampling periods on file for Hamler Village since 2016, the first ending in 2018; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Hamler Village sent EPA, 317 lines are counted.

Service lines in the inventory
MaterialLines
Lead0
Galvanized, needing replacement0
Unknown material0
Not lead317
All lines317

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

Ohio EPA's own statewide sampling tested 1 plant of Hamler Village (latest sample August 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

Ohio EPA's current sampling status map lists 1 plant of Hamler Village as sampled, most recently February 2026.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Hamler Village's samples in 2019, the last year it was sampled, was 62.7 µg/L. The worst yearly average was 62.7 µg/L and the highest single sample was 108 µg/L, from 51 samples taken from 2012 to 2019.

For HAA5, the average in the last year sampled was 8.1 µg/L. The worst yearly average was 12 µg/L and the highest single sample was 26.9 µg/L, from 51 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L62.7 µg/L (2019)62.7 µg/L108 µg/L51
HAA560 µg/L8.1 µg/L12 µg/L26.9 µg/L51

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate: the highest of 10 samples was 2.95 mg/L (as nitrogen) in 2013; in 2019, the last year sampled, nitrate was not detected. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.

Arsenic was not detected in 3 samples (limit 10 µg/L).

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)102.95 mg/L10 mg/L0
Arsenic3not detected10 µg/L0
Combined radium11.3 pCi/L5 pCi/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. carbon tetrachloride was detected in 1 of 3 samples, highest 0.54 µg/L (limit 5). Benzene, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 3 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L30 of 3not detected0
Carbon tetrachloride5 µg/L31 of 30.54 µg/L0
1,2-dichloroethane5 µg/L30 of 3not detected0
Trichloroethylene (TCE)5 µg/L30 of 3not detected0
Tetrachloroethylene (PCE)5 µg/L30 of 3not detected0
Vinyl chloride2 µg/L30 of 3not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 3 of 3 samples, highest 22 µg/L (limit 2,000). Not detected: atrazine, alachlor, chromium, cadmium, mercury, selenium, and thallium, in 3 samples each.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L30 of 3not detected0
AlachlorFarm chemical2 µg/L30 of 3not detected0
ChromiumMetal100 µg/L30 of 3not detected0
CadmiumMetal5 µg/L30 of 3not detected0
BariumMetal2,000 µg/L33 of 322 µg/L0
MercuryMetal2 µg/L30 of 3not detected0
SeleniumMetal50 µg/L30 of 3not detected0
ThalliumMetal2 µg/L30 of 3not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 0 of 185 routine total coliform samples taken in the distribution system at Hamler Village tested positive (0%); in 2019, the last year on file, 0 of 19 did.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Hamler Village has fluoride from natural sources at a level higher than what is needed to prevent tooth decay. The level it reports is 2.47 mg/L.

EPA's treatment table lists no fluoridation step at Hamler Village.

Measured fluoride: 2.39 mg/L on average at the plant's entry points in 2018 (high enough that children under 9 can get mottled teeth); samples ran from 2.39 to 2.54 mg/L across 3 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

Water and sewer bills

Ohio EPA's 2023 rate survey puts the water bill at Hamler Village for a household using 5,000 gallons a month at $888 a year, about $74 a month.

The sewer bill in the same survey is $924 a year at 5,000 gallons a month.

Annual bills, 2023
UseWater, per yearSewer, per year
2,500 gallons a month$633$669
5,000 gallons a month$888$924
8,000 gallons a month$1,194$1,230

The survey lists it as “Hamler”. These are inside-city rates and annual bills at the use shown.

Source: Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State University, May 2025).

How well the service area is mapped

EPA estimated the service area of Hamler Village with a computer model rather than drawing it from the utility's map, so its edges are approximate.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

On the map

Show this system's territory on the map — 1 ZIP code in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH3500312 (EPA ECHO).

Quick answers

Where does Hamler Village get its water?

Hamler Village treats its own water from Groundwater wells (2 wells).

How many people does Hamler Village serve?

Hamler Village serves about 580 people, and is the main water system for 1 ZIP code.

Who owns Hamler Village?

Hamler Village is owned by a local government.

Cite this page

Cite this page as:

Cracked Buckeye, "Hamler Village · OH3500312", https://crackedbuckeye.com/water/OH3500312/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31