Water system

Middlefield Mobile Home Park

EPA ID OH2801912 · Geauga County · 400 people served

Groundwater wells (11 wells)
Groundwater

Middlefield Mobile Home Park treats its own water from Groundwater wells (11 wells).

The system's record

Groundwater wells (11 wells)
Groundwater
Wells: EPA lists 11 active wells. ODNR well logs locate 2 public-supply wells inside Middlefield Mobile Home Park's wellhead protection zone, 183 to 243 ft deep, in sandstone & shale and shale. Zoom in to see them as dots.
Well 1Well 3Well 8Well 9Well 10Well 11Well 12Well 13Well 14Well 15Well 16
Active wells
11
Serves
400 people · Geauga County
EPA ID
OH2801912

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 0 ppb in 2025 (action level 15 ppb).

EPA health-based violations since 2015:

  • 2018Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.082 MG/L (limit 0.08 MG/L) · returned to compliance

5 violations of any kind logged since 2020: 4 for required testing that was missed or reported late; 1 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Present in 1 ZIP code

Serves

No ZIP code has Middlefield Mobile Home Park on record as its main water supplier.

Also present in 1 more ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Middlefield Mobile Home Park does not buy water from another system on record; it treats its own source water.

No other system is on record buying water from Middlefield Mobile Home Park.

What the records show about Middlefield Mobile Home Park

Who runs it

EPA's record says Middlefield Mobile Home Park has 154 service connections and serves 400 people.

EPA classes it as a community water system, one that serves the same residents all year.

Its office telephone on EPA's record is 440-251-9587.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Middlefield Mobile Home Park: chlorine disinfection and iron and manganese removal.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA counts 1 health-based violation for Middlefield Mobile Home Park since 2015. Health-based means a contaminant above its legal limit or a required treatment step not carried out. It falls into 1 separate problem (one contaminant or rule in one year); the table lists it.

EPA logs 5 violations of any kind since 2020: 4 for required testing that was missed or reported late; 1 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Health-based violations since 2015, most recent first
YearContaminant or ruleKindMeasuredLimitStatus in EPA's record
2018Total trihalomethanes (TTHM)above the legal limit on average0.082 mg/L0.08 mg/Lreturned to compliance

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Middlefield Mobile Home Park was 0 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027. A result of 0 means at least nine in ten of the homes sampled had no lead detected.

The highest result on file is 5 ppb, in the period ending December 2018.

EPA has 8 sampling periods on file for Middlefield Mobile Home Park since 2016, the first ending in 2018; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Middlefield Mobile Home Park sent EPA, 150 lines are counted.

Service lines in the inventory
MaterialLines
Lead0
Galvanized, needing replacement0
Unknown material0
Not lead150
All lines150

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

Ohio EPA's own statewide sampling tested 1 plant of Middlefield Mobile Home Park (latest sample July 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

Ohio EPA's current sampling status map lists 1 plant of Middlefield Mobile Home Park as sampled, most recently May 2026.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Middlefield Mobile Home Park's samples in 2019, the last year it was sampled, was 3.5 µg/L. The worst yearly average was 146 µg/L and the highest single sample was 146 µg/L, from 20 samples taken from 2012 to 2019. A yearly average over 80 is not itself a violation, because compliance is judged site by site.

For HAA5, the average in the last year sampled was 0 µg/L. The worst yearly average was 55.1 µg/L and the highest single sample was 55.9 µg/L, from 20 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L3.5 µg/L (2019)146 µg/L146 µg/L20
HAA560 µg/L0 µg/L55.1 µg/L55.9 µg/L20

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate: the highest of 8 samples was 0.18 mg/L (as nitrogen), in 2019, the last year sampled. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.

Arsenic: the highest of 2 samples was 3 µg/L (limit 10); detections averaged 2.5; none over the limit.

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)80.18 mg/L10 mg/L0
Arsenic23 µg/L10 µg/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 2 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L20 of 2not detected0
Carbon tetrachloride5 µg/L20 of 2not detected0
1,2-dichloroethane5 µg/L20 of 2not detected0
Trichloroethylene (TCE)5 µg/L20 of 2not detected0
Tetrachloroethylene (PCE)5 µg/L20 of 2not detected0
Vinyl chloride2 µg/L20 of 2not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Not detected: atrazine in 3 samples, alachlor in 3 samples, chromium in 2 samples, cadmium in 2 samples, barium in 2 samples, mercury in 2 samples, selenium in 2 samples, thallium in 2 samples.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L30 of 3not detected0
AlachlorFarm chemical2 µg/L30 of 3not detected0
ChromiumMetal100 µg/L20 of 2not detected0
CadmiumMetal5 µg/L20 of 2not detected0
BariumMetal2,000 µg/L20 of 2not detected0
MercuryMetal2 µg/L20 of 2not detected0
SeleniumMetal50 µg/L20 of 2not detected0
ThalliumMetal2 µg/L20 of 2not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 2 of 96 routine total coliform samples taken in the distribution system at Middlefield Mobile Home Park tested positive (2.08%); in 2019, the last year on file, 1 of 12 did. E. coli was never found in the 54 samples tested for it.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Middlefield Mobile Home Park has fluoride from natural sources at the recommended level for preventing tooth decay. The level it reports is 0.77 mg/L.

EPA's treatment table lists no fluoridation step at Middlefield Mobile Home Park.

Measured fluoride: 0.77 mg/L on average at the plant's entry points in 2017 (in the range dentists aim for); samples ran from 0.69 to 0.77 mg/L across 2 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

How well the service area is mapped

EPA drew the service area of Middlefield Mobile Home Park from parcel data.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

On the map

Show this system's territory on the map — 1 ZIP code in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH2801912 (EPA ECHO).

Quick answers

Where does Middlefield Mobile Home Park get its water?

Middlefield Mobile Home Park treats its own water from Groundwater wells (11 wells).

How many people does Middlefield Mobile Home Park serve?

Middlefield Mobile Home Park serves about 400 people.

Cite this page

Cite this page as:

Cracked Buckeye, "Middlefield Mobile Home Park · OH2801912", https://crackedbuckeye.com/water/OH2801912/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31