Water system

Bradford Village

EPA ID OH1900212 · Darke County · 2,000 people served · owned by a local government

Groundwater wells (3 wells)
Groundwater

Bradford Village treats its own water from Groundwater wells (3 wells).

The system's record

Groundwater wells (3 wells)
Groundwater
Wells: EPA lists 3 active wells. ODNR well logs locate 2 public-supply wells inside Bradford Village's wellhead protection zone, 110 to 123 ft deep, in sand & gravel and gravel/sand/clay. Zoom in to see them as dots.
Well 2Well 3Well 4
Active wells
3
Serves
2,000 people · Darke County
EPA ID
OH1900212

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 7.8 ppb in 2025 (action level 15 ppb).

EPA record: no health-based violations since 2015.

3 violations of any kind logged since 2020: 1 for required testing that was missed or reported late; 2 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Present in 1 ZIP code

Serves

Main water supplier in 1 ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Bradford Village does not buy water from another system on record; it treats its own source water.

No other system is on record buying water from Bradford Village.

What the records show about Bradford Village

Who runs it

EPA's record describes Bradford Village as owned by a local government. It has 780 service connections and serves 2,000 people.

EPA classes it as a community water system, one that serves the same residents all year.

Its office telephone on EPA's record is 937-448-2718.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Bradford Village: aeration, chlorine disinfection, iron and manganese removal, ion-exchange softening, and sand or media filtration.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA's record shows no health-based violations for Bradford Village since 2015.

EPA logs 3 violations of any kind since 2020: 1 for required testing that was missed or reported late; 2 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Bradford Village was 7.8 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027.

EPA has 5 sampling periods on file for Bradford Village since 2016, the first ending in 2017; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Bradford Village sent EPA, 781 lines are counted.

Service lines in the inventory
MaterialLines
Lead1
Galvanized, needing replacement2
Unknown material318
Not lead460
All lines781

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

EPA's fifth national round of testing (UCMR 5) took 2 samples of the water entering the pipes of Bradford Village in 2024 and measured 29 PFAS. No PFAS was detected, PFOA and PFOS (federal limit 4 ng/L each) among them.

Ohio EPA's own statewide sampling tested 1 plant of Bradford Village (latest sample August 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Bradford Village's samples in 2019, the last year it was sampled, was 0 µg/L. The worst yearly average was 42.2 µg/L and the highest single sample was 43.2 µg/L, from 14 samples taken from 2013 to 2019.

For HAA5, the average in the last year sampled was 0 µg/L. The worst yearly average was 5 µg/L and the highest single sample was 10.1 µg/L, from 14 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L0 µg/L (2019)42.2 µg/L43.2 µg/L14
HAA560 µg/L0 µg/L5 µg/L10.1 µg/L14

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate: the highest of 9 samples was 1.8 mg/L (as nitrogen) in 2013; in 2019, the last year sampled, nitrate was not detected. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.

Arsenic: the highest of 13 samples was 3.6 µg/L (limit 10); detections averaged 3.5; none over the limit.

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)91.8 mg/L10 mg/L0
Arsenic133.6 µg/L10 µg/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 2 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L20 of 2not detected0
Carbon tetrachloride5 µg/L20 of 2not detected0
1,2-dichloroethane5 µg/L20 of 2not detected0
Trichloroethylene (TCE)5 µg/L20 of 2not detected0
Tetrachloroethylene (PCE)5 µg/L20 of 2not detected0
Vinyl chloride2 µg/L20 of 2not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 2 of 2 samples, highest 92.5 µg/L (limit 2,000). Not detected: atrazine, alachlor, chromium, cadmium, mercury, selenium, and thallium, in 2 samples each.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L20 of 2not detected0
AlachlorFarm chemical2 µg/L20 of 2not detected0
ChromiumMetal100 µg/L20 of 2not detected0
CadmiumMetal5 µg/L20 of 2not detected0
BariumMetal2,000 µg/L22 of 292.5 µg/L0
MercuryMetal2 µg/L20 of 2not detected0
SeleniumMetal50 µg/L20 of 2not detected0
ThalliumMetal2 µg/L20 of 2not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 0 of 197 routine total coliform samples taken in the distribution system at Bradford Village tested positive (0%); in 2019, the last year on file, 0 of 25 did.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Bradford Village has fluoride from natural sources at the recommended level for preventing tooth decay. The level it reports is 0.68 mg/L.

EPA's treatment table lists no fluoridation step at Bradford Village.

Measured fluoride: 0.58 mg/L on average at the plant's entry points in 2017 (below the 0.7 mg/L target); samples ran from 0.51 to 0.58 mg/L across 2 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

Lithium

Lithium was not detected in 2 UCMR 5 samples at Bradford Village, last sampled in 2024 (the method reports from 9 µg/L).

Lithium is not regulated. EPA's draft health reference level is 10 µg/L, and it occurs naturally in deep groundwater, so well systems in the northwest run highest.

Source: EPA UCMR 5 occurrence data (final release, August 2026), samples from 2023 to 2025.

How well the service area is mapped

EPA estimated the service area of Bradford Village with a computer model rather than drawing it from the utility's map, so its edges are approximate.

Counting the people who live in the ZIP codes it overlaps, this atlas estimates 1,798 residents are inside the boundary, 90% of the 2,000 people Bradford Village reports serving.

The resident count is an estimate from 2020 Census ZIP-code populations, not a count of customers.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

On the map

Show this system's territory on the map — 1 ZIP code in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH1900212 (EPA ECHO).

Quick answers

Where does Bradford Village get its water?

Bradford Village treats its own water from Groundwater wells (3 wells).

How many people does Bradford Village serve?

Bradford Village serves about 2,000 people, and is the main water system for 1 ZIP code.

Who owns Bradford Village?

Bradford Village is owned by a local government.

Cite this page

Cite this page as:

Cracked Buckeye, "Bradford Village · OH1900212", https://crackedbuckeye.com/water/OH1900212/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31