Water system

Auburn Skilled Nursing & Rehabilitation

EPA ID OH1502712 · Columbiana County · 50 people served

Groundwater wells (2 wells)
Groundwater

Auburn Skilled Nursing & Rehabilitation treats its own water from Groundwater wells (2 wells).

The system's record

Groundwater wells (2 wells)
Groundwater
Wells: EPA lists 2 active wells.
Well 2Well 1
Active wells
2
Serves
50 people · Columbiana County
EPA ID
OH1502712

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 0 ppb in 2025 (action level 15 ppb).

EPA record: no health-based violations since 2015.

3 violations of any kind logged since 2020: 2 for required testing that was missed or reported late; 1 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Present in 0 ZIP codes

Serves

No ZIP code has Auburn Skilled Nursing & Rehabilitation on record as its main water supplier.

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Auburn Skilled Nursing & Rehabilitation does not buy water from another system on record; it treats its own source water.

No other system is on record buying water from Auburn Skilled Nursing & Rehabilitation.

What the records show about Auburn Skilled Nursing & Rehabilitation

Who runs it

EPA's record says Auburn Skilled Nursing & Rehabilitation has 1 service connection and serves 50 people.

EPA classes it as a community water system, one that serves the same residents all year.

EPA's record says it has substantially implemented source water protection under Ohio's program, dating the program from 2025. Its office telephone on EPA's record is 330-537-4621.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Auburn Skilled Nursing & Rehabilitation: corrosion control, chlorine disinfection, and ion-exchange softening.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA's record shows no health-based violations for Auburn Skilled Nursing & Rehabilitation since 2015.

EPA logs 3 violations of any kind since 2020: 2 for required testing that was missed or reported late; 1 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Auburn Skilled Nursing & Rehabilitation was 0 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027. A result of 0 means at least nine in ten of the homes sampled had no lead detected.

The highest result on file is 2.2 ppb, in the period ending June 2017.

EPA has 10 sampling periods on file for Auburn Skilled Nursing & Rehabilitation since 2016, the first ending in 2016; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Auburn Skilled Nursing & Rehabilitation sent EPA, 1 line is counted.

Service lines in the inventory
MaterialLines
Lead0
Galvanized, needing replacement0
Unknown material0
Not lead1
All lines1

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

Ohio EPA's own statewide sampling tested 1 plant of Auburn Skilled Nursing & Rehabilitation (latest sample September 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

Ohio EPA's current sampling status map lists 1 plant of Auburn Skilled Nursing & Rehabilitation as sampled, most recently August 2026.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Auburn Skilled Nursing & Rehabilitation's samples in 2019, the last year it was sampled, was 0.6 µg/L. The worst yearly average was 227 µg/L and the highest single sample was 227 µg/L, from 15 samples taken from 2013 to 2019. A yearly average over 80 is not itself a violation, because compliance is judged site by site.

For HAA5, the average in the last year sampled was 0 µg/L. The worst yearly average was 73 µg/L and the highest single sample was 145.9 µg/L, from 15 samples. A yearly average over 60 is not itself a violation, because compliance is judged site by site.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L0.6 µg/L (2019)227 µg/L227 µg/L15
HAA560 µg/L0 µg/L73 µg/L145.9 µg/L15

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate was not detected in 9 samples through 2019 (limit 10 mg/L as nitrogen; above 10 is unsafe for infants).

Arsenic was not detected in 2 samples (limit 10 µg/L).

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)9not detected10 mg/L0
Arsenic2not detected10 µg/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 2 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L20 of 2not detected0
Carbon tetrachloride5 µg/L20 of 2not detected0
1,2-dichloroethane5 µg/L20 of 2not detected0
Trichloroethylene (TCE)5 µg/L20 of 2not detected0
Tetrachloroethylene (PCE)5 µg/L20 of 2not detected0
Vinyl chloride2 µg/L20 of 2not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Not detected: atrazine, alachlor, chromium, cadmium, barium, mercury, selenium, and thallium, in 2 samples each.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L20 of 2not detected0
AlachlorFarm chemical2 µg/L20 of 2not detected0
ChromiumMetal100 µg/L20 of 2not detected0
CadmiumMetal5 µg/L20 of 2not detected0
BariumMetal2,000 µg/L20 of 2not detected0
MercuryMetal2 µg/L20 of 2not detected0
SeleniumMetal50 µg/L20 of 2not detected0
ThalliumMetal2 µg/L20 of 2not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 1 of 100 routine total coliform samples taken in the distribution system at Auburn Skilled Nursing & Rehabilitation tested positive (1%); in 2019, the last year on file, 0 of 12 did. E. coli was never found in the 1 sample tested for it.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Auburn Skilled Nursing & Rehabilitation has fluoride from natural sources, but at a level below what is recommended for preventing tooth decay, and does not adjust it. The level it reports is 0.19 mg/L.

EPA's treatment table lists no fluoridation step at Auburn Skilled Nursing & Rehabilitation.

Measured fluoride: 0.22 mg/L on average at the plant's entry points in 2017 (too little to protect teeth); samples ran at 0.22 mg/L across 2 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

On the map

Show this system's territory on the map — 0 ZIP codes in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH1502712 (EPA ECHO).

Quick answers

Where does Auburn Skilled Nursing & Rehabilitation get its water?

Auburn Skilled Nursing & Rehabilitation treats its own water from Groundwater wells (2 wells).

How many people does Auburn Skilled Nursing & Rehabilitation serve?

Auburn Skilled Nursing & Rehabilitation serves about 50 people.

Cite this page

Cite this page as:

Cracked Buckeye, "Auburn Skilled Nursing & Rehabilitation · OH1502712", https://crackedbuckeye.com/water/OH1502712/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31