Water system
Beverly Village
EPA ID OH8400112 · Washington County · 1,900 people served · owned by a local government
Beverly Village treats its own water from Groundwater wells (4 wells).
The system's record
- Active wells
- 4
- Serves
- 1,900 people · Washington County
- EPA ID
- OH8400112
About this area's water
Did you know
- Beverly sits on the Muskingum River in Washington County and was laid out/incorporated as a village in 1831, named for Beverly, Massachusetts, the hometown of an early settler - though this is town history, not a…
Source: genealogytrails.com
Treatment & pressure
How it is treated
Village of Beverly's public water system draws from groundwater wells (EPA SDWIS confirms source type 'GW', ~678 service connections, population served 1,900, active status). The village's water-sewer webpage does not publish specific well count, treatment process, or plant details beyond directing…
Source: data.epa.govbeverly-oh.com
Water pressure
Not published.
What it costs
We found no published rate schedule online. Sewer charges are billed based on metered water consumption (no separate sewer meters), bills are due by the 15th…
Source: beverly-oh.combeverly-oh.com
Water quality & impurities5
| Contaminant | Level | Limit | Year |
|---|---|---|---|
| Yearly water quality report (inadequate) Compliance period opened 1/25/2019, still outstanding per EPA federal SDWIS/ECHO. | N/A violation | N/A | 2019 |
| Yearly water quality report (inadequate) Two separate 'Other' violations opened 2/3/2020 and 10/21/2020, both still outstanding. | N/A violation | N/A | 2020 |
| Public notice of a violation not given Additional 'Other' violation opened 10/21/2020, still outstanding. | N/A violation | N/A | 2020 |
| Yearly water quality report (inadequate) Violation opened 12/29/2023, still outstanding as of the latest federal record. | N/A violation | N/A | 2023 |
| Coliform testing missed Short monitoring violation for June 2025, resolved same month. An earlier 2019 monitoring violation and a 2008… | N/A violation | N/A | 2025 |
Source: data.epa.gov
EPA compliance record
Lead at the tap: 90th-percentile result 1.7 ppb in 2025 (action level 15 ppb).
EPA record: no health-based violations since 2015.
5 violations of any kind logged since 2020: 1 for required testing that was missed or reported late; 4 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).
Supply stress
No specific source-adequacy or capacity information is published.
Sewers
Sanitary
Village of Beverly operates its own sanitary sewer system, billed to customers based on metered water usage (no separate sewer meters), per the village's water-sewer page.
Source: beverly-oh.com
Sourcesverified
Compiled from the utility's own reports and public records, then independently re-checked against primary sources.
Main supplier in 1 ZIP code
Serves
Main water supplier in 1 ZIP code
- 45715 · Beverly53% of residents
Also present in 1 more ZIP code
- 45786 · Waterford Township and Waterford4% of residents
Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.
Buys from · Sells to
Beverly Village does not buy water from another system on record; it treats its own source water.
No other system is on record buying water from Beverly Village.
What the records show about Beverly Village
Who runs it
EPA's record describes Beverly Village as owned by a local government. It has 678 service connections and serves 1,900 people.
EPA classes it as a community water system, one that serves the same residents all year.
Its office telephone on EPA's record is 740-984-2348.
Source: EPA Safe Drinking Water Information System (SDWIS), water system record.
How the water is treated
EPA's treatment table registers these steps for Beverly Village: chlorine disinfection.
The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.
Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).
Violations
EPA's record shows no health-based violations for Beverly Village since 2015.
EPA logs 5 violations of any kind since 2020: 1 for required testing that was missed or reported late; 4 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records).
Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).
Lead and copper at the tap
In the sampling period ending December 2025, the 90th-percentile lead result at Beverly Village was 1.7 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027.
The highest result on file is 7.8 ppb, in the period ending December 2018.
EPA has 8 sampling periods on file for Beverly Village since 2016, the first ending in 2018; no period was above 10 ppb.
Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Beverly Village sent EPA, 694 lines are counted.
| Material | Lines |
|---|---|
| Lead | 0 |
| Galvanized, needing replacement | 1 |
| Unknown material | 0 |
| Not lead | 693 |
| All lines | 694 |
Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.
EPA's dashboard status for this inventory: reported all required service line types.
Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.
PFAS
Ohio EPA's own statewide sampling tested 1 plant of Beverly Village (latest sample April 2021). The highest result was PFOA at 30.9 ppt (ppt is the same unit as ng/L), against Ohio's action level of 70 ppt. Those action levels are the ones Ohio EPA used for the survey; the 2024 federal limit for PFOA and PFOS is 4 ng/L.
Ohio EPA's current sampling status map lists 1 plant of Beverly Village as sampled, most recently June 2026.
PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.
Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.
Disinfection byproducts
Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.
For TTHM, the average of Beverly Village's samples in 2019, the last year it was sampled, was 11 µg/L. The worst yearly average was 19 µg/L and the highest single sample was 32.4 µg/L, from 14 samples taken from 2013 to 2019.
For HAA5, the average in the last year sampled was 0 µg/L. The worst yearly average was 4.5 µg/L and the highest single sample was 8.9 µg/L, from 14 samples.
| Byproduct | Limit | Latest yearly average | Worst yearly average | Highest sample | Samples |
|---|---|---|---|---|---|
| TTHM | 80 µg/L | 11 µg/L (2019) | 19 µg/L | 32.4 µg/L | 14 |
| HAA5 | 60 µg/L | 0 µg/L | 4.5 µg/L | 8.9 µg/L | 14 |
A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).
Nitrate, arsenic and radioactivity
Nitrate: the highest of 8 samples was 6.7 mg/L (as nitrogen) in 2012; in 2019, the last year sampled, the highest was 5.67 mg/L. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.
Arsenic was not detected in 3 samples (limit 10 µg/L).
| Contaminant | Samples | Highest result | Limit | Samples over limit |
|---|---|---|---|---|
| Nitrate (as nitrogen) | 8 | 6.7 mg/L | 10 mg/L | 0 |
| Arsenic | 3 | not detected | 10 µg/L | 0 |
Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Solvents and fuels
EPA's file holds results for all six solvent and fuel compounds it checked. tetrachloroethylene (PCE) was detected in 5 of 32 samples, highest 0.9 µg/L (limit 5). Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, and vinyl chloride were not detected in 32 samples each.
| Compound | Limit | Samples | Detected in | Highest result | Samples over limit |
|---|---|---|---|---|---|
| Benzene | 5 µg/L | 32 | 0 of 32 | not detected | 0 |
| Carbon tetrachloride | 5 µg/L | 32 | 0 of 32 | not detected | 0 |
| 1,2-dichloroethane | 5 µg/L | 32 | 0 of 32 | not detected | 0 |
| Trichloroethylene (TCE) | 5 µg/L | 32 | 0 of 32 | not detected | 0 |
| Tetrachloroethylene (PCE) | 5 µg/L | 32 | 5 of 32 | 0.9 µg/L | 0 |
| Vinyl chloride | 2 µg/L | 32 | 0 of 32 | not detected | 0 |
"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Farm chemicals and metals
EPA's file holds results for all nine herbicides and metals it checked. Detected: barium in 3 of 3 samples, highest 75.6 µg/L (limit 2,000). Not detected: atrazine, alachlor, 2,4-D, chromium, cadmium, mercury, selenium, and thallium, in 3 samples each.
| Substance | Kind | Limit | Samples | Detected in | Highest result | Samples over limit |
|---|---|---|---|---|---|---|
| Atrazine | Farm chemical | 3 µg/L | 3 | 0 of 3 | not detected | 0 |
| Alachlor | Farm chemical | 2 µg/L | 3 | 0 of 3 | not detected | 0 |
| 2,4-D | Farm chemical | 70 µg/L | 3 | 0 of 3 | not detected | 0 |
| Chromium | Metal | 100 µg/L | 3 | 0 of 3 | not detected | 0 |
| Cadmium | Metal | 5 µg/L | 3 | 0 of 3 | not detected | 0 |
| Barium | Metal | 2,000 µg/L | 3 | 3 of 3 | 75.6 µg/L | 0 |
| Mercury | Metal | 2 µg/L | 3 | 0 of 3 | not detected | 0 |
| Selenium | Metal | 50 µg/L | 3 | 0 of 3 | not detected | 0 |
| Thallium | Metal | 2 µg/L | 3 | 0 of 3 | not detected | 0 |
Non-detects count as zero in the highest-result column.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Bacteria in the pipes
From 2012 to 2019, 0 of 191 routine total coliform samples taken in the distribution system at Beverly Village tested positive (0%); in 2019, the last year on file, 0 of 22 did.
A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.
Fluoride
The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Beverly Village has fluoride from natural sources, but at a level below what is recommended for preventing tooth decay, and does not adjust it. The level it reports is 0.11 mg/L.
EPA's treatment table lists no fluoridation step at Beverly Village.
Measured fluoride: none was detected in 3 samples at the plant's entry points in 2012 to 2019.
The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.
Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.
How well the service area is mapped
EPA estimated the service area of Beverly Village with a computer model rather than drawing it from the utility's map, so its edges are approximate.
Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.
Photograph
On the map
Show this system's territory on the map — 2 ZIP codes in all.
Sources
U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey
EPA's own record for this system: Enforcement and Compliance History report for OH8400112 (EPA ECHO).
Notable facts: genealogytrails.com
Water quality: data.epa.gov
Rates: beverly-oh.com, beverly-oh.com
Sewers: beverly-oh.com
Treatment: data.epa.gov, beverly-oh.com