Water system

Evergreen Poplar Village MHP

EPA ID OH7401212 · Seneca County · 128 people served

Groundwater wells (2 wells)
Groundwater

Evergreen Poplar Village MHP treats its own water from Groundwater wells (2 wells).

The system's record

Groundwater wells (2 wells)
Groundwater
Wells: EPA lists 2 active wells.
Well 1Well 3
Active wells
2
Serves
128 people · Seneca County
EPA ID
OH7401212

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 2.9 ppb in 2025 (action level 15 ppb).

EPA health-based violations since 2015:

  • 2024Lead and Copper Rule Revisions · lead service line inventory missing or incomplete (a records requirement, not a lead test result) · returned to compliance

7 violations of any kind logged since 2020: 2 for required testing that was missed or reported late; 4 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 1 health-based.

Present in 1 ZIP code

Serves

No ZIP code has Evergreen Poplar Village MHP on record as its main water supplier.

Also present in 1 more ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Evergreen Poplar Village MHP does not buy water from another system on record; it treats its own source water.

No other system is on record buying water from Evergreen Poplar Village MHP.

What the records show about Evergreen Poplar Village MHP

Who runs it

EPA's record says Evergreen Poplar Village MHP has 90 service connections and serves 128 people.

EPA classes it as a community water system, one that serves the same residents all year.

Its office telephone on EPA's record is 844-430-1320.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

EPA's treatment table registers these steps for Evergreen Poplar Village MHP: chlorine disinfection and iron and manganese removal.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA counts 1 health-based violation for Evergreen Poplar Village MHP since 2015. Health-based means a contaminant above its legal limit or a required treatment step not carried out. It falls into 1 separate problem (one contaminant or rule in one year); the table lists it.

EPA logs 7 violations of any kind since 2020: 2 for required testing that was missed or reported late; 4 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 1 health-based.

Health-based violations since 2015, most recent first
YearContaminant or ruleKindMeasuredLimitStatus in EPA's record
2024Lead and Copper Rule Revisionslead service line inventory missing or incomplete (a records requirement, not a lead test result)not on filenot on filereturned to compliance

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2025, the 90th-percentile lead result at Evergreen Poplar Village MHP was 2.9 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027.

The highest result on file is 4.6 ppb, in the period ending December 2024.

EPA has 9 sampling periods on file for Evergreen Poplar Village MHP since 2016, the first ending in 2016; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Evergreen Poplar Village MHP sent EPA, 63 lines are counted.

Service lines in the inventory
MaterialLines
Lead0
Galvanized, needing replacement0
Unknown material63
Not lead0
All lines63

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

Ohio EPA's own statewide sampling tested 1 plant of Evergreen Poplar Village MHP (latest sample September 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Evergreen Poplar Village MHP's samples in 2019, the last year it was sampled, was 0 µg/L. The worst yearly average was 9.1 µg/L and the highest single sample was 9.1 µg/L, from 7 samples taken from 2013 to 2019.

For HAA5, the average in the last year sampled was 0 µg/L. The worst yearly average was 1.2 µg/L and the highest single sample was 1.2 µg/L, from 7 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L0 µg/L (2019)9.1 µg/L9.1 µg/L7
HAA560 µg/L0 µg/L1.2 µg/L1.2 µg/L7

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

Nitrate was not detected in 13 samples through 2019 (limit 10 mg/L as nitrogen; above 10 is unsafe for infants).

Arsenic: the highest of 56 samples was 19 µg/L (limit 10); detections averaged 6.4; 2 over the limit.

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)13not detected10 mg/L0
Arsenic5619 µg/L10 µg/L2
Combined radium2not detected5 pCi/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Solvents and fuels

EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 5 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L50 of 5not detected0
Carbon tetrachloride5 µg/L50 of 5not detected0
1,2-dichloroethane5 µg/L50 of 5not detected0
Trichloroethylene (TCE)5 µg/L50 of 5not detected0
Tetrachloroethylene (PCE)5 µg/L50 of 5not detected0
Vinyl chloride2 µg/L50 of 5not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Farm chemicals and metals

EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 5 of 5 samples, highest 15 µg/L (limit 2,000). Not detected: atrazine, alachlor, chromium, cadmium, mercury, selenium, and thallium, in 5 samples each.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L50 of 5not detected0
AlachlorFarm chemical2 µg/L50 of 5not detected0
ChromiumMetal100 µg/L50 of 5not detected0
CadmiumMetal5 µg/L50 of 5not detected0
BariumMetal2,000 µg/L55 of 515 µg/L0
MercuryMetal2 µg/L50 of 5not detected0
SeleniumMetal50 µg/L50 of 5not detected0
ThalliumMetal2 µg/L50 of 5not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.

Bacteria in the pipes

From 2012 to 2019, 1 of 98 routine total coliform samples taken in the distribution system at Evergreen Poplar Village MHP tested positive (1.02%); in 2019, the last year on file, 0 of 12 did. E. coli was never found in the 1 sample tested for it.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Evergreen Poplar Village MHP has fluoride from natural sources at the recommended level for preventing tooth decay. The level it reports is 0.63 mg/L.

EPA's treatment table lists no fluoridation step at Evergreen Poplar Village MHP.

Measured fluoride: 0.61 mg/L on average at the plant's entry points in 2019 (in the range dentists aim for); samples ran from 0.61 to 0.69 mg/L across 5 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

How well the service area is mapped

EPA drew the service area of Evergreen Poplar Village MHP from parcel data.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

On the map

Show this system's territory on the map — 1 ZIP code in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH7401212 (EPA ECHO).

Quick answers

Where does Evergreen Poplar Village MHP get its water?

Evergreen Poplar Village MHP treats its own water from Groundwater wells (2 wells).

How many people does Evergreen Poplar Village MHP serve?

Evergreen Poplar Village MHP serves about 128 people.

Cite this page

Cite this page as:

Cracked Buckeye, "Evergreen Poplar Village MHP · OH7401212", https://crackedbuckeye.com/water/OH7401212/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31