Water system
Attica Village
EPA ID OH7400011 · Seneca County · 1,148 people served · owned by a local government
Attica Village treats its own water from Honey Creek (via 2 storage reservoirs).
The system's record
- Water bodies
- Honey Creek
- Raw intakes
- Honey Creek
- Serves
- 1,148 people · Seneca County
- EPA ID
- OH7400011
About this area's water
Water quality & impurities
EPA compliance record
Lead at the tap: 90th-percentile result 5.6 ppb in 2025 (action level 15 ppb).
EPA health-based violations since 2015:
- 2025Interim Enhanced Surface Water Treatment Rule · turbidity above the monthly limit; turbidity above the limit in a single reading · returned to compliance
- 2025Lead and Copper Rule · water quality limits for corrosion control not met · known
- 2023Long Term 2 Enhanced Surface Water Treatment Rule · required treatment not met · returned to compliance
EPA's count of 5 includes 2 repeat quarterly violations of the problems listed.
20 violations of any kind logged since 2020: 9 for required testing that was missed or reported late; 6 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 5 health-based.
Present in 1 ZIP code
Serves
Main water supplier in 1 ZIP code
- 44807 · Attica44% of residents
Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.
Buys from · Sells to
Attica Village does not buy water from another system on record; it treats its own source water.
No other system is on record buying water from Attica Village.
What the records show about Attica Village
Who runs it
EPA's record describes Attica Village as owned by a local government. It has 530 service connections and serves 1,148 people.
EPA classes it as a community water system, one that serves the same residents all year.
Source: EPA Safe Drinking Water Information System (SDWIS), water system record.
How the water is treated
EPA's treatment table registers these steps for Attica Village: chloramine disinfection, corrosion control, coagulation and settling, chlorine disinfection, iron and manganese removal, fluoridation, powdered activated carbon, and sand or media filtration.
The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.
Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).
Violations
EPA counts 5 health-based violations for Attica Village since 2015. Health-based means a contaminant above its legal limit or a required treatment step not carried out. They fall into 3 separate problems (one contaminant or rule in one year); the table lists them all.
EPA logs a violation for each compliance period a problem lasts, so the count of 5 includes 2 repeat entries of the problems listed.
EPA logs 20 violations of any kind since 2020: 9 for required testing that was missed or reported late; 6 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 5 health-based.
| Year | Contaminant or rule | Kind | Measured | Limit | Status in EPA's record |
|---|---|---|---|---|---|
| 2025 | Interim Enhanced Surface Water Treatment Rule | turbidity above the monthly limit; turbidity above the limit in a single reading | not on file | not on file | returned to compliance |
| 2025 | Lead and Copper Rule | water quality limits for corrosion control not met | not on file | not on file | known |
| 2023 | Long Term 2 Enhanced Surface Water Treatment Rule | required treatment not met | not on file | not on file | returned to compliance |
Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).
Lead and copper at the tap
In the sampling period ending December 2025, the 90th-percentile lead result at Attica Village was 5.6 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027.
The highest result on file is 9.2 ppb, in the period ending December 2017.
EPA has 10 sampling periods on file for Attica Village since 2016, the first ending in 2016; no period was above 10 ppb.
Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Attica Village sent EPA, 580 lines are counted.
| Material | Lines |
|---|---|
| Lead | 18 |
| Galvanized, needing replacement | 4 |
| Unknown material | 551 |
| Not lead | 7 |
| All lines | 580 |
Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.
EPA's dashboard status for this inventory: reported all required service line types.
Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.
PFAS
Ohio EPA's own statewide sampling tested 1 plant of Attica Village (latest sample September 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.
Ohio EPA's current sampling status map lists 1 plant of Attica Village as sampled, most recently May 2026.
PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.
Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.
Disinfection byproducts
Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.
For TTHM, the average of Attica Village's samples in 2019, the last year it was sampled, was 62.6 µg/L. The worst yearly average was 68 µg/L and the highest single sample was 117 µg/L, from 69 samples taken from 2012 to 2019.
For HAA5, the average in the last year sampled was 34.7 µg/L. The worst yearly average was 40.5 µg/L and the highest single sample was 56.6 µg/L, from 69 samples.
| Byproduct | Limit | Latest yearly average | Worst yearly average | Highest sample | Samples |
|---|---|---|---|---|---|
| TTHM | 80 µg/L | 62.6 µg/L (2019) | 68 µg/L | 117 µg/L | 69 |
| HAA5 | 60 µg/L | 34.7 µg/L | 40.5 µg/L | 56.6 µg/L | 69 |
A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).
Nitrate, arsenic and radioactivity
Nitrate: the highest of 107 samples was 2.43 mg/L (as nitrogen), in 2019, the last year sampled. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.
Arsenic was not detected in 8 samples (limit 10 µg/L).
| Contaminant | Samples | Highest result | Limit | Samples over limit |
|---|---|---|---|---|
| Nitrate (as nitrogen) | 107 | 2.43 mg/L | 10 mg/L | 0 |
| Arsenic | 8 | not detected | 10 µg/L | 0 |
| Combined radium | 1 | not detected | 5 pCi/L | 0 |
Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Solvents and fuels
EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 8 samples each.
| Compound | Limit | Samples | Detected in | Highest result | Samples over limit |
|---|---|---|---|---|---|
| Benzene | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Carbon tetrachloride | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| 1,2-dichloroethane | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Trichloroethylene (TCE) | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Tetrachloroethylene (PCE) | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Vinyl chloride | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Farm chemicals and metals
EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: atrazine in 4 of 20 samples, highest 0.42 µg/L (limit 3). Not detected: alachlor in 20 samples, chromium in 8 samples, cadmium in 8 samples, barium in 8 samples, mercury in 8 samples, selenium in 8 samples, thallium in 8 samples.
| Substance | Kind | Limit | Samples | Detected in | Highest result | Samples over limit |
|---|---|---|---|---|---|---|
| Atrazine | Farm chemical | 3 µg/L | 20 | 4 of 20 | 0.42 µg/L | 0 |
| Alachlor | Farm chemical | 2 µg/L | 20 | 0 of 20 | not detected | 0 |
| Chromium | Metal | 100 µg/L | 8 | 0 of 8 | not detected | 0 |
| Cadmium | Metal | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Barium | Metal | 2,000 µg/L | 8 | 0 of 8 | not detected | 0 |
| Mercury | Metal | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
| Selenium | Metal | 50 µg/L | 8 | 0 of 8 | not detected | 0 |
| Thallium | Metal | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
Non-detects count as zero in the highest-result column.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Bacteria in the pipes
From 2012 to 2019, 1 of 388 routine total coliform samples taken in the distribution system at Attica Village tested positive (0.26%); in 2019, the last year on file, 0 of 49 did. E. coli was never found in the 1 sample tested for it.
A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.
Fluoride
The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Attica Village adjusts the fluoride level to the recommended level for preventing tooth decay.
EPA's treatment table lists fluoridation among the steps at Attica Village.
Measured fluoride: 1.01 mg/L on average at the plant's entry points in 2019 (in the range dentists aim for); samples ran from 0.76 to 1.13 mg/L across 8 samples in 2012 to 2019.
The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.
Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.
Algal toxins
Ohio EPA tests for microcystin, a toxin that harmful algal blooms can release, in raw water at the intake and in treated water.
At the intake, microcystin was detected 47 times in 270 raw-water samples, across 5 bloom seasons (2017 to 2021); the highest raw-water result was 30.05 µg/L on October 29, 2018. There has been no raw-water detection since 2024.
Microcystin was never detected in treated water (160 samples).
In all, 430 samples from 2016 to 2026, the latest on August 25, 2026.
| Water | Samples | Detections | Highest result |
|---|---|---|---|
| Raw water, at the intake | 270 | 47 | 30.05 µg/L |
| Treated water | 160 | 0 | not detected |
The ten-day advisory levels for treated water are 0.3 µg/L for children under six and 1.6 µg/L for everyone else. Any detection at the intake triggers more frequent testing until two clean weeks.
Source: Ohio EPA public water system harmful algal bloom monitoring, 2016 to present (HAB data, fetched September 2026).
How well the service area is mapped
EPA estimated the service area of Attica Village with a computer model rather than drawing it from the utility's map, so its edges are approximate.
Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.
On the map
Show this system's territory on the map — 1 ZIP code in all.
Sources
U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey
EPA's own record for this system: Enforcement and Compliance History report for OH7400011 (EPA ECHO).
Attica Village's own pages: waterutilityreport.com, dam.assets.ohio.gov