Water system
New Lexington
EPA ID OH6400411 · Perry County · 5,161 people served · owned by a local government
New Lexington treats its own water from New Lexington Reservoir(s) (Old & New Reservoir).
The system's record
- Water bodies
- New Lexington Reservoir (New), New Lexington Reservoir (Old)
- Raw intakes
- Reservoir
- Serves
- 5,161 people · Perry County
- EPA ID
- OH6400411
About this area's water

Did you know
- New Lexington drinks from two small reservoirs it owns outright — the New Lexington Reservoir and Rush Creek Reservoir Site 1B — rather than a river, a lake or a well field.
- Founder James Comly laid out 64 lots in 1817 and sold them for $25 to $50 each; forty years later the village beat Somerset and Rehoboth in a bitter fight for the county seat.
- The village will credit your sewer bill $25 to $125 for filling a swimming pool — as long as you call the water office before you turn the hose on.
- Water and sewer rates here rise 3% automatically every year, an escalator written into the ordinance and running since June 1, 2010.
- The 2025 drinking water report lists a TTHM annual average of 99.8 ppb next to an 80 ppb federal limit, and still prints 'NO' in the violation column.
Source: files-backend.assets.thrillshare.comen.wikipedia.orgnewlexingtonohio.gov
History6
- 1817New Lexington established by James Comly, who laid out 64 lots and sold them for $25 to $50 apiece.
- 1857New Lexington won the Perry County seat after a bitter contest with Somerset and Rehoboth.
- 2021Ordinance 21-12, passed October 4, 2021, set the current published water and sewer rate schedule, keeping the automatic 3% annual increase that has applied every year since June 1, 2010.
- 2023-2024Seven consecutive quarters of Total Organic Carbon treatment-technique violations, Q2 2023 through Q4 2024. The village's public notice of January 30, 2025 cites Ohio Administrative Code 3745-81-77…
- 2024Two TTHM maximum contaminant level violations. A notice distributed August 30, 2024 covered a four-quarter average of 0.087 mg/L; a second, distributed December 2, 2024 for the fourth quarter…
- 2026Mid-August flooding across Perry, Muskingum and Morgan counties. Heavy rainfall stirred sediment inside the water system, prompting a boil advisory that was upgraded to a full boil alert on about…
Source: en.wikipedia.orgfiles-backend.assets.thrillshare.comfiles-backend.assets.thrillshare.com
Treatment & pressure
How it is treated
The village treats its own surface water at the New Lexington Water Treatment Plant, drawing from the New Lexington Reservoir and Rush Creek Reservoir Site 1B — both are in use and, in the village's words, require extensive treatment. The 2025 report publishes no description of the treatment train…
Source: files-backend.assets.thrillshare.comfiles-backend.assets.thrillshare.comdata.epa.gov
Water pressure
Not published. No psi figures or pressure-zone information appear in the drinking water reports, the water department page or the rate ordinances.
Source: files-backend.assets.thrillshare.comnewlexingtonohio.gov
What it costs
$7.65 per 1,000 gallons
Typical household bill about $43 a month for water.
From Ordinance 21-12, passed October 4, 2021 — the most recent rate schedule the village publishes. Water base rate $20.11 per month for the first 1,000 gallons, then $7.65 per…
Source: files-backend.assets.thrillshare.comnewlexingtonohio.gov
Water quality & impurities10
| Contaminant | Level | Limit | Year |
|---|---|---|---|
| TTHM (Total Trihalomethanes) Range 75.5-107.7. The reported annual average is above the 80 ppb federal limit, yet the 2025 report's violation column… | 99.8 ppb | 80 (MCL) | 2025 |
| HAA5 (Haloacetic Acids) Range 9.3-45.5. No violation. | 37.8 ppb | 60 (MCL) | 2025 |
| Total Organic Carbon (removal ratio) The report's own definition says a value below 1 indicates a violation of the TOC removal requirements; the reported… | <0.7 ratio | 1.0 minimum (TT) | 2025 |
| Turbidity Highest recorded result for the year; 100% of samples met the standard in the lowest month. | 0.28 NTU | 1 NTU maximum… | 2025 |
| Nitrate (as N) Range <0.1-0.29. | 0.29 ppm | 10 (MCL) | 2025 |
| Fluoride Range 0.96-1.19. | 1.19 ppm | 4 (MCL) | 2025 |
| Barium Range 0.16-0.16; drilling waste, metal refinery discharge, natural deposits. | 0.16 ppm | 2 (MCL) | 2025 |
| Chlorine Range 0.8-2.0. | 2.0 ppm | 4 (MRDL) | 2025 |
| Lead (90th percentile) All results reported as <2.0. Zero samples exceeded the action level. Lead is tested every three years. | 0 ppb | 15 (action… | 2025 |
| Copper (90th percentile) Zero samples exceeded the action level. Copper is tested every three years. | 0.020 ppm | 1.3 (action… | 2025 |
Source: files-backend.assets.thrillshare.comdata.epa.gov
EPA compliance record
Lead at the tap: 90th-percentile result 0 ppb in 2025 (action level 15 ppb).
EPA health-based violations since 2015:
- 2024Total organic carbon · did not remove enough organic matter before disinfecting · returned to compliance
- 2024Total trihalomethanes (TTHM) · above the legal limit on average · measured 0.089 MG/L (limit 0.08 MG/L) · returned to compliance
- 2023Total organic carbon · did not remove enough organic matter before disinfecting · returned to compliance
EPA's count of 9 includes 6 repeat quarterly violations of the problems listed.
14 violations of any kind logged since 2020: 1 for required testing that was missed or reported late; 4 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 9 health-based.
Projects & plans3
Recent and current work
- GAC filter repair · 2024 · completed
The granular activated carbon filter was repaired November 20, 2024 and returned to service November 21, 2024, after the fourth-quarter TTHM MCL violation. - Treatment adjustments for Total Organic Carbon removal · 2025 · completed
The village told customers in its January 30, 2025 notice that it was making adjustments to the treatment process to increase TOC removal. Ohio EPA recorded a…
Source: files-backend.assets.thrillshare.comfiles-backend.assets.thrillshare.comdata.epa.gov
Planned or needed
- Post-flood water system recovery and assessment · 2026 · needed
After the August 2026 flooding and the sediment-driven boil alert, resilience work at the reservoirs and plant is implied but no capital plan, cost or schedule…
Supply stress
High for a system this size. New Lexington depends entirely on two small surface reservoirs it owns, and its own source assessment lists what sits in the protection area: runoff from truck storage, auto repair and salvage yards, agricultural runoff, oil and gas wells, abandoned mines, and stream crossings where a vehicle accident can…
Source: files-backend.assets.thrillshare.comdata.epa.govnewlexingtonohio.gov
Sewers
Sanitary
The village runs and bills its own sanitary sewer system alongside water; Ordinance 21-12 sets sewer at $34.67 per month for the first 1,000 gallons and $7.03 per 1,000 thereafter, with 55% added outside the corporation limits, and Ordinances 18-10 and 23-11 govern summer pool-fill sewer credits of $25 to $125. Water charges are a lien…
Storm
Nothing published. No stormwater utility, fee or drainage program appears on the village site. The only relevant public record is the August 2026 regional flooding, which brought Ohio National Guard and ODOT debris removal crews to Perry, Muskingum and Morgan…
Source: files-backend.assets.thrillshare.comnewlexingtonohio.govnewlexingtonohio.gov
Sourcesverified
Compiled from the utility's own reports and public records, then independently re-checked against primary sources.
Main supplier in 1 ZIP code
Serves
Main water supplier in 1 ZIP code
- 43764 · New Lexington56% of residents
Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.
Buys from · Sells to
New Lexington does not buy water from another system on record; it treats its own source water.
No other system is on record buying water from New Lexington.
What the records show about New Lexington
Who runs it
EPA's record describes New Lexington as owned by a local government. It has 1,985 service connections and serves 5,161 people.
EPA classes it as a community water system, one that serves the same residents all year.
EPA's record says it has substantially implemented source water protection under Ohio's program, dating the program from 2023. Its office telephone on EPA's record is 740-324-1633.
Source: EPA Safe Drinking Water Information System (SDWIS), water system record.
How the water is treated
EPA's treatment table registers these steps for New Lexington: corrosion control, coagulation and settling, chlorine disinfection, iron and manganese removal, fluoridation, granular activated carbon, and sand or media filtration.
The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.
Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).
Violations
EPA counts 9 health-based violations for New Lexington since 2015. Health-based means a contaminant above its legal limit or a required treatment step not carried out. They fall into 3 separate problems (one contaminant or rule in one year); the table lists them all.
EPA logs a violation for each compliance period a problem lasts, so the count of 9 includes 6 repeat entries of the problems listed.
EPA logs 14 violations of any kind since 2020: 1 for required testing that was missed or reported late; 4 for a report, record or notice that was missing, late or incomplete (the yearly water quality report, a public notice, lead line records); 9 health-based.
| Year | Contaminant or rule | Kind | Measured | Limit | Status in EPA's record |
|---|---|---|---|---|---|
| 2024 | Total organic carbon | did not remove enough organic matter before disinfecting | not on file | not on file | returned to compliance |
| 2024 | Total trihalomethanes (TTHM) | above the legal limit on average | 0.089 mg/L | 0.08 mg/L | returned to compliance |
| 2023 | Total organic carbon | did not remove enough organic matter before disinfecting | not on file | not on file | returned to compliance |
Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).
Lead and copper at the tap
In the sampling period ending December 2025, the 90th-percentile lead result at New Lexington was 0 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027. A result of 0 means at least nine in ten of the homes sampled had no lead detected.
The highest result on file is 1.1 ppb, in the period ending December 2021.
EPA has 7 sampling periods on file for New Lexington since 2016, the first ending in 2018; no period was above 10 ppb.
Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory New Lexington sent EPA, 3,525 lines are counted.
| Material | Lines |
|---|---|
| Lead | 3 |
| Galvanized, needing replacement | 0 |
| Unknown material | 3,402 |
| Not lead | 120 |
| All lines | 3,525 |
Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.
EPA's dashboard status for this inventory: reported all required service line types.
Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.
PFAS
EPA's fifth national round of testing (UCMR 5) took 4 samples of the water entering the pipes of New Lexington in 2024 and measured 29 PFAS. No PFAS was detected, PFOA and PFOS (federal limit 4 ng/L each) among them.
Ohio EPA's own statewide sampling tested 1 plant of New Lexington (latest sample September 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.
PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.
Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.
Disinfection byproducts
Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.
For TTHM, the average of New Lexington's samples in 2019, the last year it was sampled, was 56.8 µg/L. The worst yearly average was 62.9 µg/L and the highest single sample was 104.7 µg/L, from 60 samples taken from 2012 to 2019.
For HAA5, the average in the last year sampled was 14.8 µg/L. The worst yearly average was 18.6 µg/L and the highest single sample was 40.1 µg/L, from 60 samples.
| Byproduct | Limit | Latest yearly average | Worst yearly average | Highest sample | Samples |
|---|---|---|---|---|---|
| TTHM | 80 µg/L | 56.8 µg/L (2019) | 62.9 µg/L | 104.7 µg/L | 60 |
| HAA5 | 60 µg/L | 14.8 µg/L | 18.6 µg/L | 40.1 µg/L | 60 |
A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).
Nitrate, arsenic and radioactivity
Nitrate: the highest of 97 samples was 1.85 mg/L (as nitrogen) in 2012; in 2019, the last year sampled, the highest was 1.26 mg/L. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.
Arsenic was not detected in 8 samples (limit 10 µg/L).
| Contaminant | Samples | Highest result | Limit | Samples over limit |
|---|---|---|---|---|
| Nitrate (as nitrogen) | 97 | 1.85 mg/L | 10 mg/L | 0 |
| Arsenic | 8 | not detected | 10 µg/L | 0 |
Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Solvents and fuels
EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 8 samples each.
| Compound | Limit | Samples | Detected in | Highest result | Samples over limit |
|---|---|---|---|---|---|
| Benzene | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Carbon tetrachloride | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| 1,2-dichloroethane | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Trichloroethylene (TCE) | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Tetrachloroethylene (PCE) | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Vinyl chloride | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Farm chemicals and metals
EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 7 of 8 samples, highest 16.3 µg/L (limit 2,000). Not detected: atrazine, alachlor, chromium, cadmium, mercury, selenium, and thallium, in 8 samples each.
| Substance | Kind | Limit | Samples | Detected in | Highest result | Samples over limit |
|---|---|---|---|---|---|---|
| Atrazine | Farm chemical | 3 µg/L | 8 | 0 of 8 | not detected | 0 |
| Alachlor | Farm chemical | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
| Chromium | Metal | 100 µg/L | 8 | 0 of 8 | not detected | 0 |
| Cadmium | Metal | 5 µg/L | 8 | 0 of 8 | not detected | 0 |
| Barium | Metal | 2,000 µg/L | 8 | 7 of 8 | 16.3 µg/L | 0 |
| Mercury | Metal | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
| Selenium | Metal | 50 µg/L | 8 | 0 of 8 | not detected | 0 |
| Thallium | Metal | 2 µg/L | 8 | 0 of 8 | not detected | 0 |
Non-detects count as zero in the highest-result column.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water.
Bacteria in the pipes
From 2012 to 2019, 0 of 550 routine total coliform samples taken in the distribution system at New Lexington tested positive (0%); in 2019, the last year on file, 0 of 72 did.
A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.
Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.
Fluoride
The Ohio Department of Health's report to the CDC (My Water's Fluoride) says New Lexington adjusts the fluoride level to the recommended level for preventing tooth decay.
EPA's treatment table lists fluoridation among the steps at New Lexington.
Measured fluoride: 1.03 mg/L on average at the plant's entry points in 2019 (in the range dentists aim for); samples ran from 0 to 1.57 mg/L across 8 samples in 2012 to 2019.
The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.
Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.
Lithium
Lithium was not detected in 4 UCMR 5 samples at New Lexington, last sampled in 2024 (the method reports from 9 µg/L).
Lithium is not regulated. EPA's draft health reference level is 10 µg/L, and it occurs naturally in deep groundwater, so well systems in the northwest run highest.
Source: EPA UCMR 5 occurrence data (final release, August 2026), samples from 2023 to 2025.
Algal toxins
Ohio EPA tests for microcystin, a toxin that harmful algal blooms can release, in raw water at the intake and in treated water.
At the intake, microcystin was detected 7 times in 219 raw-water samples, across 3 bloom seasons (2016 to 2025); the highest raw-water result was 0.513 µg/L on November 25, 2024. The highest raw-water result since 2024 was 0.513 µg/L.
Microcystin was never detected in treated water (78 samples).
In all, 297 samples from 2016 to 2026, the latest on August 25, 2026.
| Water | Samples | Detections | Highest result |
|---|---|---|---|
| Raw water, at the intake | 219 | 7 | 0.513 µg/L |
| Treated water | 78 | 0 | not detected |
The ten-day advisory levels for treated water are 0.3 µg/L for children under six and 1.6 µg/L for everyone else. Any detection at the intake triggers more frequent testing until two clean weeks.
Source: Ohio EPA public water system harmful algal bloom monitoring, 2016 to present (HAB data, fetched September 2026).
Water and sewer bills
Ohio EPA's 2023 rate survey puts the water bill at New Lexington for a household using 5,000 gallons a month at $646 a year, about $54 a month.
The sewer bill in the same survey is $799 a year at 5,000 gallons a month.
| Use | Water, per year | Sewer, per year |
|---|---|---|
| 2,500 gallons a month | $402 | $576 |
| 5,000 gallons a month | $646 | $799 |
| 8,000 gallons a month | $938 | $1,068 |
The survey lists it as “New Lexington”. These are inside-city rates and annual bills at the use shown.
Source: Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State University, May 2025).
How well the service area is mapped
EPA estimated the service area of New Lexington with a computer model rather than drawing it from the utility's map, so its edges are approximate.
Counting the people who live in the ZIP codes it overlaps, this atlas estimates 4,607 residents are inside the boundary, 89% of the 5,161 people New Lexington reports serving.
The resident count is an estimate from 2020 Census ZIP-code populations, not a count of customers.
Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.
Photograph
On the map
Show this system's territory on the map — 1 ZIP code in all.
Sources
U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey
EPA's own record for this system: Enforcement and Compliance History report for OH6400411 (EPA ECHO).
New Lexington's own pages: ohio.hometownlocator.com, newlexingtonohio.gov
Notable facts: files-backend.assets.thrillshare.com, en.wikipedia.org, newlexingtonohio.gov, files-backend.assets.thrillshare.com
History: en.wikipedia.org, files-backend.assets.thrillshare.com, files-backend.assets.thrillshare.com, data.epa.gov
Water quality: files-backend.assets.thrillshare.com, data.epa.gov
Planned work: newlexingtonohio.gov, newlexingtonohio.gov
Water pressure: files-backend.assets.thrillshare.com, newlexingtonohio.gov
Capital projects: files-backend.assets.thrillshare.com, files-backend.assets.thrillshare.com, data.epa.gov
Rates: files-backend.assets.thrillshare.com, newlexingtonohio.gov
Sewers: files-backend.assets.thrillshare.com, newlexingtonohio.gov, newlexingtonohio.gov
Treatment: files-backend.assets.thrillshare.com, files-backend.assets.thrillshare.com, data.epa.gov, data.epa.gov
Supply stress: files-backend.assets.thrillshare.com, data.epa.gov, newlexingtonohio.gov