Water system

Carroll Village

EPA ID OH2300312 · Fairfield County · 524 people served · owned by a local government

Groundwater wells (2 wells)
Groundwater

Carroll Village buys its water from Little Walnut Water Treatment Facility.

The system's record

Groundwater wells (2 wells)
Groundwater
Carroll Village buys its water from Little Walnut Water Treatment Facility. Little Walnut Water Treatment Facility treats groundwater from Groundwater wells (2 wells).
Wells: EPA lists 2 active wells.
Well 1Well 3
Active wells
2
Serves
1,428 people · Fairfield County
EPA ID
OH2303212

About this area's water

Water quality & impurities

EPA compliance record

Lead at the tap: 90th-percentile result 0 ppb in 2024 (action level 15 ppb).

EPA record: no health-based violations since 2015.

EPA compliance record · Little Walnut Water Treatment Facility (treats the water)

Lead at the tap: 90th-percentile result 0 ppb in 2025 (action level 15 ppb).

EPA record: no health-based violations since 2015.

Present in 1 ZIP code

Serves

Main water supplier in 1 ZIP code

Population-weighted resident shares; a ZIP code can have more than one system on record. Recomputed from each ZIP's own system list, not from the map's cached footprint.

Buys from · Sells to

Carroll Village buys its water from Little Walnut Water Treatment Facility.

No other system is on record buying water from Carroll Village.

What the records show about Carroll Village

Who runs it

EPA's record describes Carroll Village as owned by a local government. It has 265 service connections and serves 524 people.

EPA classes it as a community water system, one that serves the same residents all year.

Its office telephone on EPA's record is 740-756-4031.

Source: EPA Safe Drinking Water Information System (SDWIS), water system record.

How the water is treated

Carroll Village buys water that Little Walnut Water Treatment Facility treats first, so the steps that count are the seller's. EPA's treatment table registers these steps for Little Walnut Water Treatment Facility: aeration, corrosion control, chlorine disinfection, fluoridation, ion-exchange softening, and sand or media filtration.

Carroll Village adds nothing of its own on that table.

The list is what each system registered with EPA for treatment plants EPA still shows as active, and it can lag a plant upgrade.

Source: EPA Safe Drinking Water Information System (SDWIS) treatment table (EPA Envirofacts, pulled September 2026).

Violations

EPA's record shows no health-based violations for Carroll Village since 2015.

EPA logs no violations of any kind for Carroll Village since 2020.

Source: EPA Safe Drinking Water Information System (SDWIS) violation records: health-based violations with compliance periods beginning in 2015 or later, all violations from 2020 or later (EPA Envirofacts, pulled September 2026).

Lead and copper at the tap

In the sampling period ending December 2024, the 90th-percentile lead result at Carroll Village was 0 ppb, under both the current 15 ppb action level and the 10 ppb level that applies from 2027. A result of 0 means at least nine in ten of the homes sampled had no lead detected.

EPA has 3 sampling periods on file for Carroll Village since 2016, the first ending in 2018; no period was above 10 ppb.

Every water system has to inventory its service lines, the pipes from the main to each building. In the inventory Carroll Village sent EPA, 225 lines are counted.

Service lines in the inventory
MaterialLines
Lead0
Galvanized, needing replacement0
Unknown material0
Not lead225
All lines225

Systems sample taps in the homes most likely to have lead pipes or solder. The 90th-percentile result is the level nine in ten of the sampled homes were at or below. Lead comes mostly from service lines and house plumbing, not the source water, so a low result for the system does not clear an old house.

EPA's dashboard status for this inventory: reported all required service line types.

Source: EPA Safe Drinking Water Information System (SDWIS) lead and copper 90th-percentile results (EPA Envirofacts), sampling periods ending 2016 or later; EPA's service line inventory dashboard, Ohio's 2026 Q2 submission.

PFAS

The water Carroll Village buys is treated by Little Walnut Water Treatment Facility, so the results below are Little Walnut Water Treatment Facility's.

Ohio EPA's own statewide sampling tested 1 plant of Little Walnut Water Treatment Facility (latest sample August 2020). Not one of the six PFAS tested (PFOA, PFOS, PFHxS, PFNA, GenX and PFBS) was detected.

Ohio EPA's current sampling status map lists 1 plant of Little Walnut Water Treatment Facility as sampled, most recently May 2026.

PFAS are the 'forever chemicals' from firefighting foam, plating shops and non-stick coatings. Results are for water leaving the plant, not your tap.

Source: EPA UCMR 5 occurrence data (final release, August 2026); Ohio EPA statewide PFAS sampling, 2019 to 2021, and its sampling status map.

Disinfection byproducts

Chlorine that disinfects water also reacts with organic matter to form byproducts. Two groups have federal limits: total trihalomethanes (TTHM, 80 µg/L) and five haloacetic acids (HAA5, 60 µg/L), judged on running yearly averages at each sampling site.

For TTHM, the average of Carroll Village's samples in 2019, the last year it was sampled, was 17.4 µg/L. The worst yearly average was 24.9 µg/L and the highest single sample was 31.5 µg/L, from 16 samples taken from 2012 to 2019.

For HAA5, the average in the last year sampled was 3.1 µg/L. The worst yearly average was 7.4 µg/L and the highest single sample was 9.9 µg/L, from 16 samples.

Disinfection byproducts in the distribution system
ByproductLimitLatest yearly averageWorst yearly averageHighest sampleSamples
TTHM80 µg/L17.4 µg/L (2019)24.9 µg/L31.5 µg/L16
HAA560 µg/L3.1 µg/L7.4 µg/L9.9 µg/L16

A yearly average of 0 means nothing was detected in that year's samples. EPA's file stops at 2019; Ohio EPA's Drinking Water Watch has newer results.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system samples (non-detects counted as zero).

Nitrate, arsenic and radioactivity

The water Carroll Village buys is treated by Little Walnut Water Treatment Facility, so the results below are Little Walnut Water Treatment Facility's.

Nitrate: the highest of 8 samples was 0.29 mg/L (as nitrogen) in 2012; in 2019, the last year sampled, nitrate was not detected. No sample was over the limit of 10 mg/L. Nitrate above 10 is unsafe for infants.

Arsenic was not detected in 2 samples (limit 10 µg/L).

Nitrate, arsenic and radioactivity in finished water, 2012 to 2019
ContaminantSamplesHighest resultLimitSamples over limit
Nitrate (as nitrogen)80.29 mg/L10 mg/L0
Arsenic2not detected10 µg/L0

Measured in finished water: at the plant's entry points and in the distribution system; raw well and intake samples are left out. Non-detects count as zero.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water of Little Walnut Water Treatment Facility.

Solvents and fuels

The water Carroll Village buys is treated by Little Walnut Water Treatment Facility, so the results below are Little Walnut Water Treatment Facility's.

EPA's file holds results for all six solvent and fuel compounds it checked. Benzene, carbon tetrachloride, 1,2-dichloroethane, trichloroethylene, tetrachloroethylene, and vinyl chloride were not detected in 2 samples each.

Solvents and fuels in finished water, 2012 to 2019
CompoundLimitSamplesDetected inHighest resultSamples over limit
Benzene5 µg/L20 of 2not detected0
Carbon tetrachloride5 µg/L20 of 2not detected0
1,2-dichloroethane5 µg/L20 of 2not detected0
Trichloroethylene (TCE)5 µg/L20 of 2not detected0
Tetrachloroethylene (PCE)5 µg/L20 of 2not detected0
Vinyl chloride2 µg/L20 of 2not detected0

"Not detected" means the lab's result was below what its method can measure, not that the compound is absent. Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water of Little Walnut Water Treatment Facility.

Farm chemicals and metals

The water Carroll Village buys is treated by Little Walnut Water Treatment Facility, so the results below are Little Walnut Water Treatment Facility's.

EPA's file holds results for 8 of the nine herbicides and metals it checked. Detected: barium in 2 of 2 samples, highest 36.3 µg/L (limit 2,000). Not detected: atrazine, alachlor, chromium, cadmium, mercury, selenium, and thallium, in 2 samples each.

Herbicides and metals in finished water, 2012 to 2019
SubstanceKindLimitSamplesDetected inHighest resultSamples over limit
AtrazineFarm chemical3 µg/L20 of 2not detected0
AlachlorFarm chemical2 µg/L20 of 2not detected0
ChromiumMetal100 µg/L20 of 2not detected0
CadmiumMetal5 µg/L20 of 2not detected0
BariumMetal2,000 µg/L22 of 236.3 µg/L0
MercuryMetal2 µg/L20 of 2not detected0
SeleniumMetal50 µg/L20 of 2not detected0
ThalliumMetal2 µg/L20 of 2not detected0

Non-detects count as zero in the highest-result column.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, finished water of Little Walnut Water Treatment Facility.

Bacteria in the pipes

From 2012 to 2019, 0 of 91 routine total coliform samples taken in the distribution system at Carroll Village tested positive (0%); in 2019, the last year on file, 0 of 12 did.

A positive coliform test is a warning sign, not a violation by itself. E. coli is a sign that human or animal waste may have reached the water. Coliform counts are routine samples only; E. coli counts include repeat samples.

Source: EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, distribution-system presence/absence tests for total coliform and E. coli.

Fluoride

The Ohio Department of Health's report to the CDC (My Water's Fluoride) says Carroll Village buys its water from Little Walnut Water Treatment Facility, a system that adjusts the fluoride level to the recommended level for preventing tooth decay.

EPA's treatment table lists fluoridation among the steps at Little Walnut Water Treatment Facility, which treats the water Carroll Village buys.

Measured fluoride: 0.99 mg/L on average leaving the plants of Little Walnut Water Treatment Facility, which supplies Carroll Village, in 2017 (in the range dentists aim for); samples ran from 0.99 to 1.03 mg/L across 2 samples in 2012 to 2019.

The recommended level for preventing tooth decay is 0.7 mg/L; the federal limit is 4 mg/L. The treatment list is what each system registered with EPA and can lag a plant upgrade.

Source: CDC My Water's Fluoride (fluoridation status as reported by the Ohio Department of Health, fetched September 2026); EPA Safe Drinking Water Information System (SDWIS) treatment table; EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, entry-point fluoride samples.

How well the service area is mapped

EPA estimated the service area of Carroll Village with a computer model rather than drawing it from the utility's map, so its edges are approximate.

Source: EPA Service Area Boundaries; resident estimate by this atlas from ZIP-code overlap.

On the map

Show this system's territory on the map — 1 ZIP code in all.

Sources

U.S. EPA SDWIS and Community Water System Service Area Boundaries (v3, 2026), Ohio EPA primacy data, 2020 census blocks: the system serving most residents, traced through purchases to the treating utility; Ohio EPA 2023 Sewer and Water Rate Survey (Ohio State, May 2025) for household bills; Ohio EPA DEFA loan awards since 2016 for the loans paragraph · EPA SDWIS · EPA service area boundaries · Ohio EPA drinking water · Ohio EPA rate survey

EPA's own record for this system: Enforcement and Compliance History report for OH2300312 (EPA ECHO).

Quick answers

Where does Carroll Village get its water?

Carroll Village buys its water from Little Walnut Water Treatment Facility.

How many people does Carroll Village serve?

Carroll Village serves about 524 people, and is the main water system for 1 ZIP code.

Who owns Carroll Village?

Carroll Village is owned by a local government.

Cite this page

Cite this page as:

Cracked Buckeye, "Carroll Village · OH2300312", https://crackedbuckeye.com/water/OH2300312/, built 2026-10-31, accessed [date].

How to cite · Report a correction · Built 2026-10-31